Diagnostics and Troubleshooting Chapter 5
Channel Diagnostics
When an input channel is enabled, the module performs a diagnostic check to see
that the channel has been properly configured. In addition, the channel is tested
on every scan for configuration errors, over-range and under-range, and
open-circuit conditions.
Invalid Channel Configuration Detection
Whenever a channel configuration word is improperly defined, the module
reports an error. See page 78
through page 81 for a description of module errors.
Over-range or Under-range Detection
Whenever the data received at the channel word is out of the defined operating
range, an over-range or under-range error is indicated in input data word 7.
Possible causes of an out-of-range condition include the:
temperature is too hot or cold for the type of thermocouple being used.
wrong thermocouple is being used for the input type selected, or for the
configuration that was programmed.
input device is faulty.
signal input from the input device is beyond the scaling range.
Open-circuit Detection
On each scan, the module performs an open-circuit test on all enabled channels.
Whenever an open-circuit condition occurs, the open-circuit bit for that channel
is set in input data word 6.
Possible causes of an open circuit include:
the input device is broken.
a wire is loose or cut.
the input device is not installed on the configured channel.
a thermocouple is installed incorrectly.