Channel Cut-off Frequency
The filter cut-off frequency, -3 dB, is the point on the frequency response curve
where frequency components of the input signal are passed with 3 dB of
attenuation. This table shows cut-off frequencies for the supported filters.
All input frequency components at or below the cut-off frequency are passed by
the digital filter with less than 3 dB of attenuation. All frequency components
above the cut-off frequency are increasingly attenuated as shown in the graphs on
page 49
.
Table 5 - Filter Frequency versus Channel Cut-off Frequency
Filter Frequency Cut-off Frequency
10 Hz 2.62 Hz
50 Hz 13.1 Hz
60 Hz 15.7 Hz
250 Hz 65.5 Hz
500 Hz 131 Hz
1 kHz 262 Hz