Chapter 4 Module Data, Status, and Channel Configuration
Channel Configuration
Each channel configuration word consists of bit fields, the settings of which
determine how the channel operates. See this table and the descriptions that
follow for valid configuration settings and their meanings.
To select Make these bit settings
1514131211109876543210
Filter frequency 10 Hz
Not used
(1)
110
60 Hz
000
50 Hz
001
250Hz
011
500 Hz
100
1 kHz
101
Open circuit Upscale
00
Downscale 01
Hold last state 10
Zero 11
Temperature
units
°C 0
°F 1
Input type Thermocouple J 0000
Thermocouple K 0001
Thermocouple T 0010
Thermocouple E 0011
Thermocouple R 0100
Thermocouple S 0101
Thermocouple B 0110
Thermocouple N 0111
Thermocouple C 1000
-50…50 mV 1001
-100…100 mV 1010
Data format Raw/proportional 000
Engineering units 001
Engineering units x 10 100
Scaled-for-PID 010
Percent range 011
Enable channel Disable 0
Enable 1
(1) An attempt to write any non-valid (spare) bit configuration into any selection field results in a module configuration error.
TIP
Default settings for a particular function are indicated by zeros.
For example, the default filter frequency is 60 Hz.