User Manual

Rockwell Automation Publication 1769-UM004B-EN-P - March 2010 31
Installation and Wiring Chapter 3
Routing field wiring in a grounded conduit can reduce electrical noise.
If field wiring must cross AC or power cables, be sure that they cross at
right angles.
If multiple power supplies are used with analog millivolt inputs, the power
supply commons must be connected.
Terminal Block Guidelines
Do not use the module’s NC terminals as connection points.
Do not tamper with or remove the CJC sensors on the terminal block.
Removal of one or both sensors will reduce accuracy.
For millivolt sensors, use Belden 8761 shielded, twisted-pair wire (or
equivalent) to be sure of proper operation and high immunity to electrical
noise.
For a thermocouple, use the shielded, twisted-pair thermocouple extension
lead wires specified by the thermocouple manufacturer. Using the incorrect
type of thermocouple extension wire or not following the correct polarity
will cause invalid readings.
To be sure of optimum accuracy, limit overall cable impedance by keeping a
cable as short as possible. Locate the module as close to input devices as the
application permits.
Grounding Guidelines
This product is intended to be mounted to a well-grounded mounting
surface such as a metal panel. Additional grounding connections from the
module’s mounting tabs or DIN rail (if used) are not required unless the
mounting surface cannot be grounded.
Keep cable shield connections to ground as short as possible.
Ground the shield drain wire at one end only. The typical location is as
follows:
For grounded thermocouples or millivolt sensors, this is at the sensor
end.
For insulated/ungrounded thermocouples, this is at the module end.
Contact your sensor manufacturer for additional details.
If it is necessary to connect the shield drain wire at the module end,
connect it to earth ground using a panel or DIN rail mounting screw.
Refer to Industrial Automation Wiring and Grounding Guidelines,
Allen-Bradley publication 1770-4.1
, for additional information.
ATTENTION: The possibility exists that a grounded or exposed
thermocouple can become shorted to a potential greater than that of the
thermocouple itself. Due to possible shock hazard, take care when wiring
grounded or exposed thermocouples. See Appendix
D, Using
Thermocouple Junctions.