Configuring Your 1769-IT6 Module with the Generic Profile for CompactLogix Controllers in RSLogix 5000 Software Appendix F
Based on the Generic Profile created earlier for 1769- IT6 module, the Controller
Tags dialog box looks like this.
Tag addresses are automatically created for configured I/O modules. All local I/O
addresses are preceded by the word Local. These addresses have the following
format:
Input Data: Local:s:I
Configuration Data: Local:s:C
Where s is the slot number assigned the I/O modules in the Generic
Profiles.
To configure an I/O module, you must open up the configuration tag for that
module by clicking the plus sign to the left of its configuration tag in the
Controller Tag database.