Owner's manual
92 Rockwell Automation Publication 1769-UM005B-EN-P - March 2012
Appendix A Module Addressing and Programming with MicroLogix 1500 and RSLogix 500
1769-IR6 Configuration File
The configuration file contains information you use to define the way a
specific channel functions. The configuration file is explained in more detail in
Configuring Channels on page 50.
The default configuration of the table is all zeros, which yields the following.
TIP
The end cap does not use a slot address.
Table 25 - Default Configuration
Parameter Default Setting
Channel Enable/Disable Disable
Input Type 100Ω Platinum 385
Data Format Raw/Proportional
Temperature Units °C (not applicable with Raw/Proportional)
Broken Input Upscale
Disable Cyclic Lead Compensation Enable
Excitation Current 1.0 mA
Input FIlter Frequency 60 Hz
0123
MicroLogix 1500
Compact I/O
Compact I/O
Compact I/O
End Cap
Slot Number