Chapter 5 Diagnostics and Troubleshooting
Module Inhibit Function
Some controllers support the module inhibit function. See your controller
manual for details.
Whenever the 1769-IR6 module is inhibited, the module continues to provide
information about changes at its inputs to the 1769 CompactBus master (for
example, a CompactLogix controller).
Module Specific
Configuration
Error
X400 010 0 0000 0000 General configuration error; no additional information
X401 010 0 0000 0001 Invalid input filter selected (channel 0)
X402 010 0 0000 0010 Invalid input filter selected (channel 1)
X403 010 0 0000 0011 Invalid input filter selected (channel 2)
X404 010 0 0000 0100 Invalid input filter selected (channel 3)
X405 010 0 0000 0101 Invalid input filter selected (channel 4)
X406 010 0 0000 0110 Invalid input filter selected (channel 5)
X407 010 0 0000 0111 Invalid input format selected (channel 0)
X408 010 0 0000 1000 Invalid input format selected (channel 1)
X409 010 0 0000 1001 Invalid input format selected (channel 2)
X40A 010 0 0000 1010 Invalid input format selected (channel 3)
X40B 010 0 0000 1011 Invalid input format selected (channel 4)
X40C 010 0 0000 1100 Invalid input format selected (channel 5)
X40D 010 0 0000 1101 Invalid excitation current for input range selected (channel 0)
X40E 010 0 0000 1110 Invalid excitation current for input range selected (channel 1)
X40F 010 0 0000 1111 Invalid excitation current for input range selected (channel 2)
X410 010 0 0001 0000 Invalid excitation current for input range selected (channel 3)
X411 010 0 0001 0001 Invalid excitation current for input range selected (channel 4)
X412 010 0 0001 0010 Invalid excitation current for input range selected (channel 5)
X413 010 0 0001 0011 Invalid calibration enable word
(1) X represents the “Don’t Care” digit.
Table 24 - Extended Error Codes
Error Type Hex
Equivalent
(1)
Module
Error
Code
Extended Error
Information
Code
Error Description
Binary Binary