Owner's manual

Rockwell Automation Publication 1769-UM005B-EN-P - March 2012 87
Diagnostics and Troubleshooting Chapter 5
Error Codes
The table below explains the extended error code.
Table 24 - Extended Error Codes
Error Type Hex
Equivalent
(1)
Module
Error
Code
Extended Error
Information
Code
Error Description
Binary Binary
No Error X000 000 0 0000 0000 No Error
General Common
Hardware Error
X200 001 0 0000 0000 General hardware error; no additional information
X201 001 0 0000 0001 Power-up reset state
Hardware-
Specific Error
X300 001 1 0000 0000 General hardware error, loss of external 24V DC power
X301 001 1 0000 0001 Hardware ROM error
X302 001 1 0000 0010 Hardware EEPROM error
X303 001 1 0000 0011 Channel 0 calibration error
X304 001 1 0000 0100 Channel 1 calibration error
X305 001 1 0000 0101 Channel 2 calibration error
X306 001 1 0000 0110 Channel 3 calibration error
X307 001 1 0000 0111 Channel 4 calibration error
X308 001 1 0000 1000 Channel 5 calibration error
X309 001 1 0000 1001 Channel 0 Analog/Digital Converter error
X30A 001 1 0000 1010 Channel 1 Analog/Digital Converter error
X30B 001 1 0000 1011 Channel 2 Analog/Digital Converter error
X30C 001 1 0000 1100 Channel 3 Analog/Digital Converter error
X30D 001 1 0000 1101 Channel 4 Analog/Digital Converter error
X30E 001 1 0000 1110 Channel 5 Analog/Digital Converter error