68 Rockwell Automation Publication 1768-UM002C-EN-P - April 2012
Chapter 5 Add, Configure, Monitor, and Replace CIP Safety I/O
Scenario 2 - Replacement Module SNN is Different from Original and Safety Signature Exists
1. Remove the old I/O module and install the new module.
2. Right-click your POINT Guard I/O module and choose Properties.
3. Click the Safety tab.
4. Click Reset Ownership.
5. Click OK.
6. Right-click your controller and choose Properties.
7. Click to the right of the safety network number to open the Safety
Network Number dialog box.