Chapter 5 Add, Configure, Monitor, and Replace CIP Safety I/O
Table 15 - Status Indicator Operation
Indicator Status Description
EtherNet/IP Modules
Module Status (MS)
Off No power.
Green, On Operating under normal conditions.
Green, Flashing Device is idle.
Red, Flashing A recoverable fault exists or a firmware update is in progress.
Red, On An unrecoverable fault exists.
Red/Green, Flashing Self-tests are in progress or the module is not configured
properly. See the network status indicator for more information.
Network Status (NS)
Off Device is not online or may not have power.
Green, On Device is online; connections are established.
Green, Flashing Device is online; no connections established.
Red, Flashing Communication timeout or a firmware update is in progress.
Red, On Communication failure. The device has detected an error that
has prevented network communication.
Red/Green, Flashing Self-test in progress.
Input Points
(INx)
Off Safety input is OFF.
Yellow, On Safety input is ON.
Red, On An error has occurred in the input circuit.
Red, Flashing When dual-channel operation is selected, an error has occurred
in the partner input circuit.
Output Points (Ox)
Off Safety output is OFF.
Yellow, On Safety output is ON.
Red, On An error has occurred in the output circuit.
Red, Flashing When dual-channel operation is selected, an error has occurred
in the partner output circuit.
IN PWR Green, Off No input power.
Green, On Input power voltage is within specification.
Yellow, On Input power voltage is out of specification.
OUT PWR Green, Off No output power.
Green, On Output power voltage is within specification.
Yellow, On Output power voltage is out of specification.
Test Output Points (Tx) Off The output is OFF.
Yellow, On The output is ON.
Red. On An error has occurred in the output circuit.