User guide

Rockwell Automation Publication 1768-UM002C-EN-P - April 2012 55
Chapter 5
Add, Configure, Monitor, and Replace
CIP Safety I/O
For more information on installation, configuration, and operation of CIP
Safety I/O modules, refer to these resources:
Guard I/O EtherNet/IP Safety Modules User Manual, publication
1791ES-UM001
POINT Guard I/O™ Safety Modules Installation and User Manual,
publication 1734-UM013
RSLogix 5000 software online help
Adding CIP Safety I/O
Modules
When you add a module to the system, you must define a configuration for the
module, including the following:
IP address for EtherNet/IP networks
To set the IP address, you can adjust the rotary switches on the module, use
DHCP software, available from Rockwell Automation, or retrieve the
default address from nonvolatile memory.
Safety network number (SNN)
See page 57
for information on setting the SNN.
Topic Page
Adding CIP Safety I/O Modules 55
Configure CIP Safety I/O Modules via RSLogix 5000 Software 56
Setting the Safety Network Number (SNN) 57
Using Unicast Connections on EtherNet/IP Networks 57
Setting the Connection Reaction Time Limit 57
Understanding the Configuration Signature 61
Reset Safety I/O Module Ownership 62
Addressing Safety I/O Data 62
Monitor Safety I/O Module Status 63
Resetting a Module to Out-of-box Condition 65
Replacing a Module 65