Installation Instructions User guide

24 CompactLogix Controllers
Publication
1768-IN004D-EN-P - December 2009
OK Off No power is applied. If MEM SAVE indicator is green,
the user program and configuration data are being
saved to flash memory.
Flashing red The controller requires a firmware update or a
firmware update is in progress.
A recoverable major fault occurred on the
controller.
A nonrecoverable major fault occurred on the
controller.
See Clear
a Major Fault on page 26.
Red The controller detected a nonrecoverable major fault so
it cleared the project from memory.
See Clear a Nonrecoverable Fault
on page 27.
Green Controller is OK.
Flashing green The controller is storing or loading a project to or from
nonvolatile memory.
CF Off There is no CompactFlash card activity.
Flashing green The controller is reading from or writing to the
CompactFlash card.
IMPORTANT: Do not remove the CompactFlash card
while the controller is reading from or writing to the
card. Removing the card during a read or write could
corrupt data on the card, data in the controller, and
firmware installed on the controller.
Flashing red The CompactFlash card does not have a valid file
system and must be replaced.
DCH0 Off Channel 0 is configured differently than the default
serial configuration.
Green Channel 0 has the default serial configuration.
CH0 Off No RS-232 activity.
Green RS-232 activity.
Controller Status Indicators
Indicator State Description