Installation Instructions CompactLogix EtherNet/IP Web Server Module Catalog Number 1768-EWEB Topic Page Important User Information 2 Minimum Spacing 7 What You Need 8 Install the Modules 8 Wire the Module 14 Connect the Module 15 Configure the Module 16 Confirm Your Installation 16 Remove the EtherNet/IP Web Server Module 17 Troubleshoot the Module 18 Status Indicators 19 Specifications 20 Additional Resources 23
CompactLogix EtherNet/IP Web Server Module Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.
CompactLogix EtherNet/IP Web Server Module 3 North American Hazardous Location Approval The following information applies when operating this equipment in hazardous locations. Informations sur l’utilisation de cet équipement en environnements dangereux. Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only.
CompactLogix EtherNet/IP Web Server Module European Hazardous Location Approval This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC. Intertek certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
CompactLogix EtherNet/IP Web Server Module 5 Environment and Enclosure ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11.
CompactLogix EtherNet/IP Web Server Module Prevent Electrostatic Discharge ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • • • • • • Touch a grounded object to discharge potential static. Wear an approved grounding wriststrap. Do not touch connectors or pins on component boards. Do not touch circuit components inside the equipment.
CompactLogix EtherNet/IP Web Server Module 7 Minimum Spacing Plan for this minimum spacing from enclosure walls, wireways, and other equipment. 1 2 2 Power OUT L1 L2/N 1 Item Description 1 105 mm (4 in.) 2 90 mm (3.54 in.) 31609-M See Specifications on page 20 for the temperature range.
CompactLogix EtherNet/IP Web Server Module What You Need Item Cat. No.
CompactLogix EtherNet/IP Web Server Module 9 If You Are Using Screws to Mount Your Modules IMPORTANT Do not use screws and DIN rail to mount the modules. It is possible to break the mounting tabs off if you screw the modules to the panel while they are on DIN rail The steps in these instructions show how to mount the modules on DIN rail. If you are using screws instead of DIN rail, make these changes to the instructions. 1.
CompactLogix EtherNet/IP Web Server Module Install the DIN Rail Mount the DIN rail in a suitable location. ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.
CompactLogix EtherNet/IP Web Server Module 11 2. Align and press the controller onto the DIN rail until the latches snap closed. Mount the EtherNet/IP Web Server Module on the DIN Rail 1. Open the DIN rail latches on the module. 2. Align and press the module onto the DIN rail to the left of the controller.
CompactLogix EtherNet/IP Web Server Module 3. Slide module snugly against the controller. Mount the Power Supply on the DIN Rail 1. Close the DIN rail latches on the power supply. 2. Align and press the power supply onto the DIN rail until the latches snap closed. 3. Slide the power supply snugly against the module. Mount the I/O Modules on the DIN Rail 1. Close the DIN rail latches on the module. 2.
CompactLogix EtherNet/IP Web Server Module 13 When the module is in place, the DIN rail latches snap closed. 2 1 2 Item Description 1 Locking tab 2 Tongue-and-groove slot 3. Slide the locking tab of the module to the left to lock the module in place. 4. Align the tongue-and-groove slots of the end-cap with the tongue-and-groove slots of the module. 5. Slide the end-cap back towards the DIN rail.
CompactLogix EtherNet/IP Web Server Module 6. Move the lock latch to the left to lock the endcap on the module. 1 Item Description 1 Lock latch Wire the Module Use an RJ45 connector to connect to the EtherNet/IP network.
CompactLogix EtherNet/IP Web Server Module 15 Connect the Module WARNING: If you connect or disconnect the cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
CompactLogix EtherNet/IP Web Server Module Configure the Module To configure your module, refer to the configuration chapter of the Web Server Modules User Manual, publication ENET-UM527. Confirm Your Installation Verify the following status indicators’ states. 1 2 2 Power OUT L1 L2/N 31608-M Item Description 1 Solid or flashing green 2 Solid green See Troubleshoot the Module on page 18 if the status indicators are in other states.
CompactLogix EtherNet/IP Web Server Module 17 Remove the EtherNet/IP Web Server Module IMPORTANT When you turn the CompactLogix power supply off, make sure you wait for all status indicators on the power supply and controller to turn off before disconnecting any part from the system. If you disconnect the CompactLogix system while the controller is still writing its program to memory, the program write will not be completed and you will lose your program. 1. Turn off power. 2.
CompactLogix EtherNet/IP Web Server Module Troubleshoot the Module The three bi-color (red/green)status indicators on the module provide diagnostic information about the module and its connections to the network. If the alphanumeric display and status indicators do not sequence through the expected states, refer to the troubleshooting tables.
CompactLogix EtherNet/IP Web Server Module 19 Status Indicators The module status indicators provides the following information: Indicator Status Description NET Off Module is not powered, or does not have an IP address. • Verify there is chassis power and the module is completely inserted into the chassis and backplane. • Make sure the module has been configured. Flashing Green Module has obtained an IP address, but has no established connections.
CompactLogix EtherNet/IP Web Server Module Specifications Technical Specifications - 1768-EWEB Attribute 1768-EWEB Backplane current 834 mA at 5.2V DC Power consumption 4.34 W Power dissipation 4.38 W Isolation (continuous-voltage rating) 30V, Functional Insulation Type, Ethernet network to system Type tested at 710V DC for 60 s Wire Size Ethernet network connections: RJ45 connector according to IEC 60603-7, 2 or 4 pair Category 5e minimum cable according to TIA 568-B.
CompactLogix EtherNet/IP Web Server Module 21 Environmental Specifications - 1768-EWEB Attribute 1768-EWEB Temperature, operating • IEC 60068-2-1 (Test Ad, Operating Cold) • IEC 60068-2-2 (Test Bd, Operating Dry Heat) • IEC 60068-2-14 (Test Nb, Operating Thermal Shock) 0…60 °C (32...
CompactLogix EtherNet/IP Web Server Module Environmental Specifications - 1768-EWEB Attribute 1768-EWEB Surge transient immunity • IEC 61000-4-5 ±2 kV line-earth(CM) on communication ports Conducted RF immunity • IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz Enclosure type rating None (open-style) Certifications Certification (when product is marked)(1) Value c-UL-us • UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
CompactLogix EtherNet/IP Web Server Module 23 Additional Resources These documents contain additional information concerning related Rockwell Automation products. Resource Description EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication ENET-UM001 Provides information about how to use EtherNet/IP modules with vrious Logix5000 controllers.
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.