ControlNet Network Channel-status Indicators
The ControlNet network channel-status indicators appear in one of the
following states:
• Steady - indicator is on continuously in the defined state.
• Alternating - the two indicators alternate between the two defined
states at the same time (applies to both indicators viewed together).
The two indicators are always in opposite states, out of phase.
• Flashing - the indicator alternates between the two defined states
(applies to each indicator viewed independent of the other). If both
indicators are flashing, they must flash together, in phase.
The ControlNet Network Channel Status Indicators table summarizes the
meanings of these states.
ControlNet Network Channel-status Indicators
Cause Action
Off No power None or apply power.
Steady red Faulted unit Cycle power or reset unit.
If fault persists, contact
Allen-Bradley representative or
distributor.
Alternating
red/green
Self-test None.
Alternating red/off Incorrect node configuration Check network address and other
ControlNet network configuration
parameters.
Off Channel disabled Program network for redundant
media, if required.
Steady green Normal operation None.
or