User Manual Manual

40 Rockwell Automation Publication 1766-UM001H-EN-P - May 2014
Chapter 3 Wire Your Controller
Figure 13 - Analog Output
Analog Channel Wiring Guidelines
Consider the following when wiring your analog channels:
The analog common (COM) is connected to earth ground inside the
module. These terminals are not electrically isolated from the system. They
are connected to chassis ground.
Analog channels are not isolated from each other.
Use Belden 8761, or equivalent, shielded wire.
Under normal conditions, the drain wire (shield) should be connected to
the metal mounting panel (earth ground). Keep the shield connection to
earth ground as short as possible.
To ensure optimum accuracy for voltage type inputs, limit overall cable
impedance by keeping all analog cables as short as possible. Locate the I/O
system as close to your voltage type sensors or actuators as possible.
The controller does not provide loop power for analog inputs. Use a power
supply that matches the transmitter specifications as shown below.
OV1O/3 O/4
O/5
O/7 O/8 O/10
O/6 O/9 O/11
OV0
3
C
DC4
VAC
DC6
VAC
COM
ANA
DC5
VAC
Output Terminal Block
Voltage Load
44680
Voltage Load