Rockwell Automation Publication 1766-UM001H-EN-P - May 2014 257
MicroLogix 1400 Distributed Network Protocol (DNP3) Appendix F
Class Level of Index 22 is 3(B38:2/0 and B38:2/1), and Class Level of other
Indexes are 0.
DNP3 Analog Output Object
The supported object group and variations are listed in this section. The
MicroLogix 1400 responds with the default group and variation when the DNP3
Master requests to read an object with Any variation.
Analog Output Status Objects:
g40v0 - Analog Output Status - Any Variations
g40v1 - Analog Output Status - 32-bit with flag (default)
g40v2 - Analog Output Status - 16-bit with flag (default)
g40v3 - Analog Output Status - Single-prec flt-pt with flag (default)
Analog Output Command Objects:
g41v1 - Analog Output - 32-bit
g41v2 - Analog Output - 16-bit
g41v3 - Analog Output - Single-prec flt-pt
Related Object File Number:
16-bit Analog Output Object File Number
32-bit Analog Output Object File Number
Short Floating Point Analog Output Object File Number
Related Configuration File Number:
- None