User Manual Manual

140 Rockwell Automation Publication 1766-UM001H-EN-P - May 2014
Appendix A Specifications
Relays Used vs. Maximum Current per Relay (24V DC) 1762-OX6I
Module Load Ratings 1762-OX6I
Volts (max.) Controlled Load (Current) per Module (max.)
240V AC 6 A
120V AC 12 A
(1)
(1) Current per relay limited to 6 A at ambient temperatures above 40 °C (104.°F).
125V DC 11.5 A
24V DC 30 A
(2)
(2) 24 A in ambient temperatures above 40 °C (104.°F). Limited by ambient temperature
and the number of relays controlling loads. See below.
123
3
4
5
6
7
8
45 6
Number of Relays Controlling Loads
Maximum Current per Relay (Amps)
Ambient Temperature
below 40 °C (104.°F)
Ambient Temperature
above 40 °C (104.°F)