User Manual Manual

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014 135
Specifications Appendix A
Hazardous environment class For 1762-IQ32T, 1762-OB32T, and 1762-OV32T modules
Hazardous Location, Class I, Division 2 Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 No. 213,
ANSI/ISA-12.12.01)
For all other modules:
Hazardous Location, Class I, Division 2 Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 No. 213) for all
modules
Radiated and conducted emissions EN50081-2 Class A
Electrical/EMC: The module has passed testing at the following levels:
ESD immunity For 1762-IQ32T, 1762-OB32T, and 1762-OV32T modules
IEC61000-4-2: 4 kV contact, 8 kV air, 4 kV indirect
For all other modules:
IEC1000-4-2: 4 kV contact, 8 kV air, 4 kV indirect
Radiated RF immunity For 1762-IQ32T, 1762-OB32T, and 1762-OV32T modules
IEC61000-4-3: 10V/m, 80…2700 MHz, 80% amplitude modulation
For all other modules:
IEC1000-4-3: 10 V/m, 80…1000 MHz, 80% amplitude modulation, +900 MHz keyed carrier for all
modules
EFT/B immunity For 1762-IQ32T, 1762-OB32T, and 1762-OV32T modules
IEC61000-4-4: 2 kV, 5 kHz on signal ports
For all other modules
IEC1000-4-4: 2 kV, 5 kHz
Surge transient immunity For 1762-IQ32T, 1762-OB32T, and 1762-OV32T modules
IEC61000-4-5: 2 kV common mode, 1 kV differential mode
For all other modules
IEC1000-4-5: 2 kV common mode, 1 kV differential mode
Conducted RF immunity For 1762-IQ32T, 1762-OB32T, and 1762-OV32T modules
IEC61000-4-6: 10V, 0.15…80 MHz
(2)
For all other modules:
IEC1000-4-6: 10V, 0.15…80 MHz
(2)
(1) For module-specific operating temperature range, refer to the Installation Instructions for the specific module.
(2) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30…1000 MHz.
General Specifications
Specification Value
Input Specifications
Specification 1762-IA8 1762-IQ8 1762-IQ16 1762-IQ32T 1762-IQ8OW6
Shipping weight, approx.
(with carton)
209 g (0.46 lbs.) 200 g (0.44 lbs.) 230 g (0.51 lbs.) 200g (0.44 lbs.) 280g (0.62 lbs.)
Voltage category 100/120V AC 24V DC (sink/source)
(1)
24V DC (sink/source)
(1)
24V DC
(sink/source)
(1)
24V DC (sink/source)
(1)
Operating voltage range 79V AC…132V AC at
47 Hz…63 Hz
10…30V DC at 30 °C
(86 °F)
10…26.4V DC at
55 °C
(131 °F)
10…30V DC
10…26.4V DC
(3)(2)
10…30V DC
(24 points) at 30 °C
(86 °F)
10…26.4V DC
(23 points)at 60 °C
(140 °F)
10…30V DC at 30 °C
(86 °F)
10…26.4V DC at
65 °C (149 °F)
Number of inputs 8 8 16 32 8
Bus current draw, max. 50 mA at 5V DC
(0.25W)
50 mA at 5V DC
(0.25W)
70 mA at 5V DC
(0.35W)
(3)
170 mA at 5V DC
0 mA at 24V DC
110 mA at 5V DC
80 mA at 24V DC