User Manual Owner's manual

Publication 1766-UM002A-EN-P - November 2008
User Provided Pages 35
HTML Examples - the following example shows an HTML code
segment with a short description of what you would see on a web
browser:
Generating Custom Data
Table Monitor Pages
You can generate Custom Data Table Monitor pages with your text
editor then download them to the MicroLogix 1400 controller using
RSLogix 500/RSLogix Micro version 8.10 or later. The first element of
the file must contain a special tag as shown here:
<!ABCDM-xx>
where xx is the automatic refresh rate in seconds (01 to 99).
A value outside the range defaults to a “snapshot” display.
You can modify the refresh rate three different ways:
enter the desired refresh rate and press the Change button
select the Default button for a 15 second refresh
disable the refresh by selecting the Disable button
Referencing Data Table Memory - the Data Table locations in the
Custom Data Table Monitor are referenced by placing custom tags into
the ASCII file of the processor. The format of the custom tag is:
<!ABDTR-file_type{file_number}:{file_element}[,#elements][%format]
[!comment]>
The items surrounded with {} are sometimes optional, whereas the
items surrounded by [] are always optional.
Examples HTML Code Web Browser Displays
Input image word I:0 <!ABDTR-I:0> the value of the first word of the
input image table in the default
format of decimal with bold type
Timer T4:0 <!ABDTR-T4:0> the values of the timer in T4:0 in
the default format of a table
Timer T4:0 <!ABDTR-T4:0%d> the values of the three words
comprising timer T4:0 in decimal
with bold type
N24:0 to N24:3 <!ABDTR-N24:0,4> the values of the four words in
N24:0 through N24:3 in decimal
with bold type
S:21 to S:23 <!ABDTR-S:21, 3%d> the values of the three words in
S:21 through S:23 in decimal with
bold type