Quick Start

Publication IASIMP-QS037A-EN-P - May 2013 19
Chapter 1
Pressure Setpoints
From the first Pressure Setpoints screen you can:
Press Pressure Setpoint to enter the desired system pressure.
Press Start Pressure to set the pressure (combined with the time
delay) at which the Lag 1 and Lag 2 pumps will come on if the
desired pressure is unable to be maintained.
View the current pressure reading (analog input must have been set
up previously).
Press Once Below Start Pressure The Next Pump Will Start in:
(Seconds) to enter the time delay in seconds between Lag pump
starts. If system pressure falls below the start set point, the Lag pump
starting is delayed by this value.
Press Off Pressure to set the system pressure point at which all of
the pumps shut off.
Press More to see the second Pressure Setpoints screen.