Manual

Publication 1764-UM001B-EN-P - April 2002
A-4 Specifications
Table A.3 Response Times for High-Speed dc Inputs 0 Through 7
(applies to 1764-24BWA and 1764-28BXB)
Maximum
High-Speed Counter
Frequency at 50%
Duty Cycle (KHz)
Filter
Setting
(ms)
Minimum
ON Delay
(ms)
Maximum
ON Delay
(ms)
Minimum
OFF Delay
(ms)
Maximum
OFF Delay
(ms)
20.000 0.025 0.005 0.025 0.005 0.025
6.700 0.075 0.040 0.075 0.045 0.075
5.000 0.100 0.050 0.100 0.060 0.100
2.000 0.250 0.170 0.250 0.210 0.250
1.000 0.500 0.370 0.500 0.330 0.500
0.500 1.000 0.700 1.000 0.800 1.000
0.250 2.000 1.700 2.000 1.600 2.000
0.125 4.000 3.400 4.000 3.600 4.000
0.063
8.000
(1)
(1) This is the default setting.
6.700 8.000 7.300 8.000
0.031 16.000 14.000 16.000 14.000 16.000
Table A.4 Response Times for Normal dc Inputs 8 Through 11 (1764-24BWA)
and 8 Through 15 (1764-28BXB)
Maximum
Frequency at 50%
Duty Cycle (kHz)
Filter
Setting
(ms)
Minimum
ON Delay
(ms)
Maximum
ON Delay
(ms)
Minimum
OFF Delay
(ms)
Maximum
OFF Delay
(ms)
1.000 0.500 0.090 0.500 0.020 0.500
0.500 1.000 0.500 1.000 0.400 1.000
0.250 2.000 1.100 2.000 1.300 2.000
0.125 4.000 2.800 4.000 2.700 4.000
0.063
8.000
(1)
(1) This is the default setting.
5.800 8.000 5.300 8.000
0.031 16.000 11.000 16.000 10.000 16.000