User Manual

MicroLogix™ 1500 Programmable Controller Base Units 7
Publication 1764-IN001B-EN-P
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or
non-hazardous locations only. The following WARNING statement applies to
use in hazardous locations.
Use only the following communication cables in Class I, Division 2 hazardous
locations.
!
WARNING
EXPLOSION HAZARD
Substitution of components may impair suitability for Class
I, Division 2.
Do not replace components or disconnect equipment unless
power has been switched off or the area is known to be
non-hazardous.
Do not connect or disconnect components unless power has
been switched off or the area is known to be non-hazardous.
This product must be installed in an enclosure. All cables
connected to the product must remain in the enclosure or be
protected by conduit or other means.
All wiring must comply with N.E.C. article 501-4(b).
Table 4 Cable Listing
Environment Classification Communication Cables
Class I, Division 2 Hazardous Environment 1761-CBL-PM02 Series C or later
1761-CBL-HM02 Series C or later
1761-CBL-AM00 Series C or later
1761-CBL-AP00 Series C or later
2707-NC8 Series B or later
2707-NC10 Series B or later
2707-NC11 Series B or later