Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or
non-hazardous locations only. The following WARNING statement applies to use in
hazardous locations.
Catalog
Number
Description
Input
Power
Digital
Inputs
Analog
Inputs
Digital
Outputs
Comm.
Ports
1763-L16AWA 120/240V ac (10) 120V ac (2) voltage input
0...10V dc
(6) relay
All individually
isolated
(1) RS-232/485
combo
(isolated)
(1) Ethernet
1763-L16BWA 120/240V ac (6) 24V dc
(4) high-speed
24V dc
(1)
(1)
The 4 high-speed inputs (inputs 0 through 3) can be used for pulse latching or higher speed counting. Refer to Input
Specifications on page 24 and the MicroLogix 1100 Instruction Set Reference Manual, publication 1763-RM001, for more
information.
(2) voltage input
0 ...10V dc
(6) relay
All individually
isolated
(1) RS-232/485
combo
(isolated)
(1) Ethernet
1763-L16BBB 24V dc (6) 24V dc
(4) high-speed
24V dc
(1)
(2) voltage input
0...10V dc
(2) relay (isolated)
(2) 24V dc FET
(2) high-speed
24V dc FET
(1) RS-232/485
combo
(isolated)
(1) Ethernet
1763-L16DWD 12/24V dc (6) 12/24V dc
(4) high-speed
12/24V dc
(1)
(2) voltage input
0...10V dc
(6) relay
All individually
isolated
(1) RS-232/485
combo
(isolated)
(1) Ethernet
WARNING
EXPLOSION HAZARD
Substitution of components may impair suitability for Class I, Division 2.
Do not replace components or disconnect equipment unless power has been
switched off.
Do not connect or disconnect components unless power has been switched off.
This product must be installed in an enclosure. All cables connected to the
product must remain in the enclosure or be protected by conduit or other means.
All wiring must comply with N.E.C. article 501-10(b).