Installation Instructions Owner's manual

26
Publication 1763-IN001B-EN-P - September 2007
Out
put Specificat
ions For Hazardous Locations Applications
(Class I, Division 2, Groups A, B, C, D)
General
Description 1763
-L16AWA, -L16BWA,
-L16DWD
-L16BBB
Relay and FET Outputs
Maximum Controlled Load 1080 VA 360 VA
Maximum Continuous Current:
Current per Group Common 3A 3A
Current per Controller at 150V max 18 A or total of per-point loads, whichever is less
at 240V max 18 A or total of per-point loads, whichever is less
Relay Outputs
Turn On Time/Turn Off Time
10 msec (maximum)
(1)
(1)
Scan time dependent.
Load Current 10 mA (minimum)
Relay Contact Ratings
Maximum Volts Amperes Amperes
Continuous
Volt-Amperes
Make Break Make Break
240V ac 7.5 A 0.75 A 3.0 A 1800 VA 180 VA
120V ac 15.0 A 1.5 A 3.0 A 1800 VA 180 VA
125V dc 0.22 A 1.0 A 28 VA