14 MicroLogix 1200 Isolated Relay Output Module
Publication 1762-IN017C-EN-P - May 2013
Module Load Ratings
Relays Used vs. Maximum Current per Relay (24V DC)
Volts (max.) Controlled Load (Current) per Module (max.)
240V AC
12 A
(1)
120V AC
12 A
(1)
(1) Current per relay limited to 6A at ambient temperatures above 40°C.
125V DC 2.4 A
24V DC
30 A
(2)
(2) 24A in ambient temperatures above 40°C. Limited by ambient temperature and the number of relays controlling loads. See
below.
IMPORTANT
Controller must be operated within Relay Contact Ratings
(page 13) and Module Load Ratings (above).
123
3
4
5
6
7
8
45 6
Number of Relays Controlling Loads
Maximum Current per Relay (Amps)
Ambient Temperature
below 40°C
Ambient Temperature
above 40°C