Manual

MicroLogix 1200 Isolated Relay Output Module 13
Publication 1762-IN017C-EN-P - May 2013
Relay Contact Ratings
Isolated Groups Outputs 0 to 5: Individually isolated
Output Group to Backplane Isolation Verified by one of the following dielectric tests:
1836V AC for 1 second or 2596V DC for 2 seconds.
265V AC working voltage (IEC Class 2 reinforced insulation)
Output Group to Output Group Isolation Verified by one of the following dielectric tests:
1836V AC for 1 second or 2596V DC for 2 seconds.
265V AC working voltage (basic insulation)
150V AC working voltage (IEC Class 2 reinforced insulation)
(1) Relay on-delay time does not include contact bounce time.
(2) This value is for reference only.
Volts (max.)
(AC:50/60 Hz)
Maximum
Amps per Point
(Resistive)
(1)
(1) The continuous current per module must be limited so the module power does not exceed 1440VA.
Pilot Duty
(2)
(2) Surge Suppression – Connecting surge suppressors across your external inductive load will extend the life of the relay
contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Voltamperes
Make Break Make Break
240V AC 5.0 A 15 A 1.5 A 3600 VA 360 VA
120V AC
7.0 A
(3)
(3) 6 A in ambient temperatures above 40°C.
30 A 3.0 A
125V DC 0.4 A 0.4 A
50 VA
(4)
(4) DC Make/Break Voltamperes must be limited to 50 VA for DC voltages between 28V DC and 125V DC. DC Make/Break
Voltamperes below 28V DC are limited by the 3 A Make/Break current limit.
24V DC
7.0 A
(3)
3.0 A
72 VA
(4)
IMPORTANT
Controller must be operated within Relay Contact Ratings (above) and
Module Load Ratings (page 14).
Output Specifications
Specification Value