Manual
MicroLogix 1200 Isolated Relay Output Module 11
Publication 1762-IN017C-EN-P - May 2013
Specifications
General Specifications
Specification Value
Dimensions, H x W x D 90 x 40 x 87 mm
height including mounting tabs is 110 mm
3.54 x 1.58 x 3.43 in.
height including mounting tabs is 4.33 in.
Approximate Shipping Weight
(with carton)
220 g (0.485 lbs.)
Temperature, nonoperating -40…85 °C (-40 …185 °F)
Temperature, operating 0…55°C (-32…131°F)
Operating humidity 5…95% non-condensing
Operating altitude 2000 m (6561 ft)
Vibration Operating: 10…500 Hz, 0.030 in. max. peak-to-peak
DIN Rail Mounting: N.O. 2.5G, N.C. 2.5G
Panel Mounting: N.O. 2.5G, N.C. 0.5G
Shock Operating: 30 g
Module power LED On: indicates power is applied.
Vendor ID Code 1
Product type code 7
Product code 124
Hazardous Environment Class Class I, Division 2, Hazardous Location, Groups A, B, C, D
ISA/ANSI12.12.01
(C-UL under CSA C22.2 No. 213)
Noise Immunity NEMA standard ICS 2-230
Radiated and Conducted Emissions EN50081-2 Class A
Electrical /EMC: The module has passed testing at the following levels:
ESD Immunity (EN61000-4-2) 4 kV contact, 8 kV air, 4 kV indirect
Radiated Immunity (EN61000-4-3) 10 V/m, 80 to 1000 MHz, 80% amplitude modulation,
Fast Transient Burst (EN61000-4-4) 2 kV, 5 kHz
Surge Immunity (EN61000-4-5) 2 kV common mode, 1 kV differential mode
Conducted Immunity (EN61000-4-6)
10V, 0.15…80 MHz
(1)
(1) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to
1000 MHz.