Instruction Manual
Publication 1762-UM001G-EN-P - March 2011
Specifications A-25
Vendor ID code 1
Product type code 7
Product code 98
Table A.32 DC-Input/Relay-Output Combination Module - 1762-IQ80W6
Environmental Specifications
Specification Value
Temperature range, operating -20…+65 °C (-4…+149 °F)
Temperature range, storage -40…+85 °C (-40…+185 °F)
Operating humidity 5…95% non-condensing
Operating altitude 2000 m (6561 ft)
Table A.33 Certifications
Certification Value
Agency certification C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
Hazardous environment class Class I, Division 2, Hazardous Location,
Groups A, B, C, D (UL 1604, C-UL under
CSA C22.2 No. 213)
Radiated and conducted emissions EN50081-2 Class A
Electrical/EMC: The module has passed testing at the
following levels:
ESD immunity (IEC1000-4-2) 4 kV contact, 8 kV air, 4 kV indirect
Radiated RF immunity
(IEC1000-4-3)
10 V/m, 80…1000 MHz, 80% amplitude
modulation, +900 MHz keyed carrier
EFT/B immunity (IEC1000-4-4) 2 kV, 5 kHz
Surge transient immunity
(IEC1000-4-5)
2 kV common mode, 1 kV differential
mode
Conducted RF immunity
(IEC1000-4-6)
10V, 0.15…80 MHz
(1)
(1) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency
range is 30…1000 MHz.
Table A.31 DC-Input/Relay-Output Combination Module - 1762-IQ80W6 General
Specifications
Specification Value