Manual

1 Publication 1762-UM002A-EN-P - July 2002
Appendix
A
Specifications
General Specifications
Specification Value
Dimensions 90 mm (height) x 87 mm (depth) x 40 mm (width)
height including mounting tabs is 110 mm
3.54 in. (height) x 3.43 in. (depth) x 1.58 in. (width)
height including mounting tabs is 4.33 in.
Approximate Shipping Weight
(with carton)
220g (0.53 lbs.)
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Operating Temperature 0°C to +55°C (32°F to +131°F)
Operating Humidity 5% to 95% non-condensing
Operating Altitude 2000 meters (6561 feet)
Vibration Operating: 10 to 500 Hz, 5G, 0.030 in. peak-to-peak
Relay Operation: 2G
Shock Operating: 30G, 11 ms panel mounted
(20G, 11 ms DIN rail mounted)
Relay Operation: 7.5G panel mounted
(5G DIN rail mounted)
Non-Operating: 40G panel mounted
(30G DIN rail mounted)
Recommended Cable Belden™ 8761 (shielded) for millivolt inputs
Shielded thermocouple extension wire for the
specific type of thermocouple you are using. Follow
thermocouple manufacturer’s recommendations.
Agency Certification C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
C-Tick marked for all applicable acts
Hazardous Environment Class Class I, Division 2, Hazardous Location, Groups A,
B, C, D (UL 1604, C-UL under CSA C22.2 No. 213)
Radiated and Conducted Emissions EN50081-2 Class A