Instruction Manual

MicroLogix 1200 Thermocouple/mV Input Module 9
Publication 1762-IN013B-EN-P - June 2013
Ground the shield drain wire at one end only. The typical location is the same point as
the sensor ground reference.
For grounded thermocouples or millivolt sensors, this is at the sensor end.
For insulated/ungrounded thermocouples, this is at the module end. Contact your
sensor manufacturer for additional details.
If it is necessary to connect the shield drain at the module end, connect it to earth
ground using a panel or DIN rail mounting screw.
Routing the field wiring in a grounded conduit can further reduce electrical noise.
Terminal Block Layout
Labeling the Terminals
A write-on label is provided with the module. Mark the identification of each terminal with
permanent ink, and slide the label back into the door.
IN1 -
IN1 +
IN 0 -
IN 0 +
IN2 -
IN2 +
CJC
CJC
IN3 -
IN3 +