B-2 Configuring the 1762-IR4 Module Using RSLogix 500
The default configuration is as follows:
Configuration Using
RSLogix 500 Version 5.50 or
Higher
This example takes you through configuring your 1762-IR4
RTD/resistance input module with RSLogix 500 programming
software. It assumes that your module is installed as expansion I/O in
a MicroLogix 1200 system, that RSLinx™ is properly configured, and
that a communications link has been established between the
MicroLogix processor and RSLogix 500.
Start RSLogix and create a MicroLogix 1200 application. The following
screen appears:
Table B.1 Default Configuration
Parameter Default Setting
Channel Enable/Disable Disable
Input Type 100Ω Platinum 385
Data Format Raw/Proportional
Temperature Units °C (not applicable with Raw/Proportional)
Broken Input Upscale
Disable Cyclic Lead Compensation Enable
Excitation Current 1.0 mA
Input FIlter Frequency 60 Hz