A-4 Specifications
Cable Specifications
RTD Standards
Description Belden #9501 Belden #9533 Belden #83503
When used? For 2-wire RTDs and
potentiometers.
For 3-wire RTDs and potentiometers.
Short runs less than 100 feet and normal
humidity levels.
For 3-wire RTDs and potentiometers.
Long runs greater than 100 feet or high
humidity levels.
Conductors 2, #24 AWG tinned copper (7 x
32)
3, #24 AWG tinned copper (7 x 32) 3, #24 AWG tinned copper (7 x 32)
Shield Beldfoil aluminum polyester
shield with copper drain wire.
Beldfoil aluminum polyester shield with
copper drain wire
Beldfoil aluminum polyester shield with
tinned braid shield.
Insulation PVC S-R PVC Teflon
Jacket Chrome PVC Chrome PVC Red Teflon
Agency
Approvals
NEC Type CM NEC Type CM NEC Art-800, Type CMP
Temperature
Rating
80°C 80°C 200°C
RTD Type
α
(3)
IEC-751 1983,
Amend. 2 1995
DIN 43760
1987
SAMA
(4)
Standard
RC21-4-1966
Japanese
Industrial
Standard JIS
C1604-1989
Japanese
Industrial
Standard JIS
C1604-1997
Minco
(5)
100 Pt 0.00385
●●
200 Pt 0.00385
●●
500 Pt 0.00385
●●
1000 Pt 0.00385
●●
100 Pt 0.03916
200 Pt 0.03916
500 Pt 0.03916
1000 Pt 0.03916
10 Cu
(1)
0.00426
120 Ni
(2)
0.00618
120 Ni 0.00672
604 NiFe 0.00518
(1) Actual value at 0°C (32°F) is 9.042 per SAMA standard RC21-4-1966.
(2) Actual value at 0°C (32°F) is100 per SAMA standard RC21-4-1966.
(3) α is the temperature coefficient of resistance which is defined as the resistance change per ohm per °C.
(4) Scientific Apparatus Makers Association
(5) Minco Type “NA” (Nickel) and Minco Type “FA” (Nickel-Iron)