Owner manual

Publication 1762-UM003A-EN-P - February 2003
A-2 Specifications
Input Specifications
Specification 1762-IR4
Input Types 100 Platinum 385
200 Platinum 385
500 Platinum 385
1000 Platinum 385
100 Platinum 3916
200 Platinum 3916
500 Platinum 3916
1000 Platinum 3916
10 Copper 426
120 Nickel 672
120 Nickel 618
604 Nickel-Iron 518
0 to 150
0 to 500
0 to 1000
0 to 3000
Bus Current Draw (max.) 40 mA at 5V dc
50 mA at 24V dc
Heat Dissipation 1.5 Total Watts (The Watts per point, plus the minimum Watts, with all points enabled.)
Converter Type Delta-Sigma
Resolution Input filter and configuration dependent.
Common Mode Rejection 110 dB minimum at 50 Hz with the 10 or 50 Hz filter selected
110 dB minimum at 60 Hz with the 10 or 60 Hz filter selected
Normal Mode Rejection Ratio 70 dB minimum at 50 Hz with the 10 or 50 Hz filter selected
70 dB minimum at 60 Hz with the 10 or 60 Hz filter selected
Non-linearity
(in percent full-scale)
±0.05%
Typical Accuracy [Autocalibration Enabled]
at 25° C (77°F) Ambient with Module
Operating Temperature at 25° C (77°F)
(1)
±0.5°C (°F) for Pt 385
±0.4°C (°F) for Pt 3916
±0.2°C (°F) for Ni
±0.3°C (°F) for NiFe
±0.6°C (°F) for Cu
±0.15 for 150 range
±0.5 for 500 range
±1.0 for 1000 range
±1.5 for 3000 range
Typical Accuracy [Autocalibration Enabled]
at 0 to 55° C (+32 to +131°F)
(1)
±0.9°C (°F) for Pt 385
±0.8°C (°F) for Pt 3916
±0.4°C (°F) for Ni
±0.5°C (°F) for NiFe
±1.1°C (°F) for Cu
±0.25 for 150 range
±0.8 for 500 range
±1.5 for 1000 range
±2.5 for 3000 range
(1) Accuracy is dependent upon the Analog/Digital converter filter rate selection, excitation current selection, data format, and input noise.