Owner manual
1 Publication 1762-UM003A-EN-P - February 2003
Appendix
A
Specifications
General Specifications
Specification Value
Dimensions 90 mm (height) x 87 mm (depth) x 40 mm (width)
height including mounting tabs is 110 mm
3.54 in. (height) x 3.43 in (depth) x 1.58 in (width)
height including mounting tabs is 4.33 in.
Approximate Shipping Weight
(with carton)
260g (0.57 lbs.)
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Operating Temperature 0°C to +55°C (32°F to +131°F)
Operating Humidity 5% to 95% non-condensing
Operating Altitude 2000 meters (6561 feet)
Vibration Operating: 10 to 500 Hz, 5G, 0.030 in. peak-to-peak
Shock Operating: 30G
Agency Certification C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
C-Tick marked for all applicable acts
Hazardous Environment Class Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL 1604, C-UL under CSA
C22.2 No. 213)
Radiated and Conducted Emissions EN50081-2 Class A
Electrical /EMC: The module has passed testing at the following levels:
• ESD Immunity (EN61000-4-2) • 4 kV contact, 8 kV air, 4 kV indirect
• Radiated Immunity (EN61000-4-3) • 10 V/m , 80 to 1000 MHz, 80% amplitude modulation, +900 MHz keyed carrier
• Fast Transient Burst (IEC1000-4-4) • 2 kV, 5kHz
• Surge Immunity (EN61000-4-5) • 1 kV galvanic gun
• Conducted Immunity (EN61000-4-6)
• 10 V, 0.15 to 80MHz
(1)
(1) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to 1000 MHz.