Owner manual

Publication 1762-UM003A-EN-P - February 2003
2-8 Installation and Wiring
Field Wiring Connections
System Wiring Guidelines
Consider the following when wiring your system:
General
This product is intended to be mounted to a well-grounded
mounting surface such as a metal panel. Additional grounding
connections from the module’s mounting tabs or DIN rail (if
used) are not required unless the mounting surface cannot be
grounded.
Channels are isolated from one another by ±10V dc maximum.
Do not use the modules NC terminals as connection points.
Route field wiring away from any other wiring and as far as
possible from sources of electrical noise, such as motors,
transformers, contactors, and ac devices. As a general rule, allow
at least 15.2 cm (6 in.) of separation for every 120V of power.
Routing field wiring in a grounded conduit can reduce electrical
noise.
If field wiring must cross ac or power cables, ensure that they
cross at right angles.
To ensure optimum accuracy, limit overall cable impedance by
keeping your cable as short as possible. Locate the I/O system
as close to your sensors or actuators as your application will
permit.
Tighten terminal screws with care. Excessive tightening can strip
a screw.
Shield Grounding
Use Belden shielded, twisted-pair wire to ensure proper
operation and high immunity to electrical noise. Refer to the
following table and the RTD Wiring Considerations below.
Under normal conditions, the drain wire and shield junction
should be connected to earth ground, via a panel or DIN rail
mounting screw at the 1762-IR4 module end.
Configuration
Recommended Cable
(1)
2-wire Belden™ 9501 or equivalent
3-wire
less than 30.48 m (100ft.)
Belden™ 9533 or equivalent
3-wire
greater than 30.48 m (100 ft.) or high
humidity conditions
Belden™ 83503 or equivalent
(1) For additional information, see page A-4.