Manual

Publication 1761-UM005B-EN-P - October 2006
50 DNI Configuration Parameters and Programming Notes
Input Messaging Considerations
You cannot write to a specific word in the DNI’s input area.
The destination offset value in the controller’s message
instruction is ignored. Data always starts at word 0.
The message length must equal the size specified by the Input
Size parameter. For DNI Series B only, both the Master’s Slave
data and the Explicit Assembly are considered to be input. For
more information, see:
Input Split Point on page 30.
Input Assembly Data (Explicit, Split Point, and Slave) on
page 67.
For MicroLogix 1000 controllers, use N7 as the destination file
type.
For other controllers, see the recommended file number on
page 41.
Status Byte
The first byte (bits 0…7) of the first word of I/O data is set aside as
status information. The second byte (bits 8…15) of the first word of
I/O is available for user data. The DNI Input/Output Image is shown
below:
Input Status to Master Device
The Input Status Byte provides the following information.
Word Input/Output Image
Series A Series B
0 0 Data (bits 8…15) Status Byte (bits 0…7)
1 1 Data Most Significant Byte (MSB) Data Least Significant Byte (LSB)
2 2 Data MSB Data LSB
3 3 Data MSB Data LSB
↓↓↓
14 30 Data MSB Data LSB
15 31 Data MSB Data LSB
Function n/a Output Buffer Overdrive n/a
Bit Number76 543210