User guide

Preface
MicroLogix 1000 Programmable Controllers User Manual
C–6
Instruction Valid Value
Ranges
Valid File TypesValid Addressing
Mode(s)
Instruction
Parameters
Description
FFL FIFO Load source
direct, indexed direct
O, I, S, B, T, C, R, N –32,768–32,767
FIFO array indexed direct O, I, S, B, N Not Applicable
FIFO control direct R (element level) Not Applicable
length (contained in the
control register)
1–128
position (contained in the
control register)
0–127
FFU FIFO Unload FIFO array indexed direct O, I, S, B, N Not Applicable
destination
direct, indexed direct
O, I, S, B, T, C, R, N Not Applicable
FIFO control direct R (element level) Not Applicable
length (contained in the
control register)
1–128
position (contained in the
control register)
0–127
FLL Fill File source direct O, I, S, B, T, C, R, N –32,768–32,767
f-min–f-max
destination indexed direct O, I, S, B, T, C, R, N
(element level)
Not Applicable
length immediate 1–128; 1–42
when destination
is T,C,R
FRD Convert from BCD source direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
destination direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
GEQ Greater Than or Equal source A direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
source B immediate, direct,
indexed direct
O, I, S, B, T, C, R, N –32,768–32,767
f-min–f-max
GRT Greater Than source A direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
source B immediate, direct,
indexed direct
O, I, S, B, T, C, R, N –32,768–32,767
f-min–f-max
Indexed
addressing is not allowed when using T
, C, or R addresses.