Cable
Selection Guide
1747-CP3
1761-CBL-AC00
Cable Length Connections from to AIC+
External
Power Supply
Required
Power Selection Switch
Setting
1747-CP3
1761 L 00
3m (9.8 ft)
c177i
SLC 5/03 or SLC 5/04 processor, channel 0 port 1 yes external
17 7 P3
1761-CBL-AC00
39f
45 cm (17.7 in)
PC COM port port 1 yes external
PanelView 550 through NULL modem adapter port 1 yes external
Port 1 on another AIC+ port 1 yes external
1761-CBL-AS03
1761-CBL-AS09
Cable Length Connections from to AIC+
External
Power Supply
Required
Power Selection Switch
Setting
1761-CBL-AS03
1761
-CB
L
-AS
09
3m (9.8 ft)
9
.5m (
31
.
17
f
t)
SLC 500 Fixed,
SLC 5/01, SLC 5/02, and SLC 5/03 processors
port 3 yes external
1761
-CB
L
-AS
09
9
.5m (
31
.
17
f
t)
PanelView 550 RJ45 port port 3 yes external
1761-CBL-AM00
1761-CBL-HM02
Cable Length Connections from to AIC+
External
Power Supply
Required
Power Selection Switch
Setting
1761-CBL-AM00 45 cm (17.7 in)
26f
MicroLogix 1000
port 2 no cable
1761 L M00
1761-CBL-HM02
c177i
2m (6.5 ft)
to port 2 on another AIC+ port 2 yes external
External power supply required unless the AIC+ is powered by the device connected to port 2, then the
selection switch should be set to cable.
Series B cables or higher are required for hardware handshaking.