Programmer (HHP) User guide

Chapter 3
Connecting the System
3–5
The table below shows connections for Belden #3106A.
For this Wire/Pair Connect this Wire To this Terminal
Shield/Drain Non-jacketed T
erminal 2 – Shield
Blue Blue Terminal 3 – (Common)
i e ra e
White with Orange Stripe Terminal 4 – (Data B)
Wh
i
t
e
/O
ra
ng
e
Orange with White Stripe Terminal 5 – (Data A)
The table below shows connections for Belden #9842.
For this Wire/Pair Connect this Wire To this Terminal
Shield/Drain Non-jacketed T
erminal 2 – Shield
eie
White with Blue Stripe
Cut back – no connection
Blu
e
/Wh
i
t
e
Blue with White Stripe Terminal 3 – (Common)
i e ra e
White with Orange Stripe Terminal 4 – (Data B)
Wh
i
t
e
/O
ra
ng
e
Orange with White Stripe Terminal 5 – (Data A)
To prevent confusion when installing the communication cable, cut back the white with blue stripe wire
immediately after the the insulation jacket is removed. This wire is not used by DH-485.
Grounding
and T
erminating the DH-485 Network
Only one connector at the end of the link must have Terminals 1 and 2
jumpered together. This provides an earth ground connection for the shield
of the communication cable.
Both ends of the network must have Terminals 5 and 6 jumpered together.
This connects the termination impedance (of 120) that is built into each
AIC+ as required by the DH-485 specification.
End-of-Line Termination
Belden
#3106A or #9842 Cable
1219 m (4000 ft) Maximum
Jumper
Jumper
Jumper