Programmer (HHP) User guide

Appendix C
Valid
Addressing Modes and File
Types
for Instruction Parameters
C–9
Instruction Valid Value
Ranges
Valid File TypesValid Addressing
Mode(s)
Instruction
Parameter
Description
SCL Scale Data source direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
rate immediate, direct,
indexed direct
O, I, S, B, T, C, R, N –32,768–32,767
offset immediate, direct,
indexed direct
O, I, S, B, T, C, R, N –32,768–32,767
destination direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
SET Set (or Output Latch)
bit address
direct O, I, S, B, T, C, R, N Not Applicable
SQC
Sequencer Compare
file indexed direct O, I, S, B, N Not Applicable
mask immediate, direct,
indexed direct
O, I, S, B, T, C, R, N –32,768–32,767
source direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
control direct R (element level) Not Applicable
length (contained in the
control register)
1–255
position (contained in the
control register)
0–255
SQL
Sequencer Load
file indexed direct O, I, S, B, N Not Applicable
source direct, indexed direct O, I, S, B, T, C, R, N –32,768–32,767
control direct R (element level) Not Applicable
length (contained in the
control register)
1–255
position (contained in the
control register)
0–255
SQO Sequencer Output file indexed direct O, I, S, B, N Not Applicable
mask direct, indexed direct O, I, S, B, T, C, R, N –32,768–32,767
destination
direct, indexed direct
O, I, S, B, T, C, R, N Not Applicable
control direct R (element level) Not Applicable
length 1–255
position 0–255
SQR Square Root source immediate, direct,
indexed direct
O, I, S, B, T, C, R, N –32,768–32,767
f-min–f-max
destination direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
STD Selectable Timed
Disable
Not Applicable
STE Selectable Timed
Enable
Not Applicable
Indexed addressing is not allowed when using T, C, or R addresses.