Programmer (HHP) User guide
Appendix C
Valid
Addressing Modes and File
Types
for Instruction Parameters
C–5
Instruction
Description Instruction
Parameters
Valid Addressing
Mode(s)
Valid File Types Valid Value
Ranges
FLL Fill File source direct O, I, S, B, T, C, R, N –32,768–32,767
f-min–f-max
destination indexed direct O, I, S, B, T, C, R, N
(element level)
Not Applicable
length immediate 1–128; 1–42
when destination
is T,C,R
FRD Convert from BCD source direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
destination direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
GEQ Greater Than or Equal
source A
direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
source B
immediate, direct,
indexed direct
O, I, S, B, T, C, R, N –32,768–32,767
f-min–f-max
GRT Greater Than
source A
direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
source B
immediate, direct,
indexed direct
O, I, S, B, T, C, R, N –32,768–32,767
f-min–f-max
HSC High-Speed Counter type immediate 0–7, where:
0=up
1=up&reset/hold
2=pulse/direction
3=pule/direction
& reset/hold
4=up/down
5=up/down &
reset/hold
6=encoder
7=encoder &
reset/hold
counter direct C5:0. C5:1
(element level)
Not Applicable
preset (contained in the
counter register)
–32,768–32,767
accum (contained in the
counter register)
–32,768–32,767
HSD HSC Interrupt Disable counter direct C Not Applicable
HSE HSC Interrupt Enable counter direct C Not Applicable
HSL HSC Load counter direct C Not Applicable
source direct B, N Not Applicable
length
always 5
IIM Immediate Input with
Mas
slot direct I Not Applicable
Mas
k
mask immediate, direct,
indexed direct
O, I, S, B, T, C, R, N –32,768–32,767
length immediate 1–10