Programmer (HHP) User guide

Appendix A
Hardware Reference
A–4
General Output Specifications
Type Relay MOSFET Triac
Voltage See Wiring Diagrams, p. 2–6.
Maximum
Load
Current
Refer to the
Relay Contact
Rating Table.
1.0A per point @ 55°
C (131
°F)
1.5A per point @ 30°C (86°F)
0.5A per point @ 55°
C (131
°F)
1.0A per point @ 30°C (86°F)
Minimum
Load
Current
10.0 mA 1 mA 10.0 mA
Current
per
Controller
1440 VA
3A for L16BBB
6A for L32BBB
1440 VA
Current
per
Common
8.0A
3A for L16BBB
6A for L32BBB
Not Applicable
Maximum
Off State
Leakage
Current
0 mA 1 mA
2 mA @ 132V ac
4.5 mA @ 264V ac
Off to On
Response
10 ms max. 0.1 ms
8.8 ms @ 60 Hz
10.6 ms @ 50 Hz
On to Off
Response
10 ms max. 1 ms 11.0 ms
Surge
Current
per Point
Not Applicable 4A for 10 ms
10A for 25 ms
Repeatability is once every 2 seconds at 55°
C (131
°F).
Relay Contact Rating Table (applies to all Bulletin 1761 controllers)
Maximum Volt
Amperes
mp r Continuou
Voltamperes
Maximum
Volt
s
Make
Break
A
mp
e
r
es
Continuou
s
Make Break
240V ac 7.5A 0.75A 2.5A 1800 VA 180 VA
120V ac 15A 1.5A
125V dc 0.22A
1.0A 28 VA
24V dc 1.2A
2.0A 28 VA
For dc voltage applications, the make/break ampere rating for relay contacts can be determined
by dividing 28 VA by the applied dc voltage. For example, 28 VA ÷ 48V dc = 0.58A. For dc
voltage applications less than 48V, the make/break ratings for relay contacts cannot exceed 2A.
For dc voltage applications greater than 48V, the make/break ratings for relay contacts cannot
exceed 1A.