Operation
The operation of the SQC instruction is shown in the figure below. The
screens shown above the figure are the condensed screens that appear after
instruction entry is complete.
P
0 1 4 S Q C F I L E
# B 8 0 0 0 0 H
P
0 1 4 S Q C M A S K
F F F 0 H
P
0 1 4 S Q C S R C
I 0 0 0 0 0 H
P
0 1 4 S Q C R 0 3
L 4 P 2
0010 0100 1001 1101
1111 1111 1111 0000
0010 0100 1001 1010
0
1
2
3
4
Step
B8
9
10
11
12
Word
Input Word I0
Mask Value FFF0
Sequencer Ref File #B8
The
SQC FD bit is set when the instruction detects that an input
word matches (thru mask) its corresponding reference word.
The
FD bit R3/FD is set in this example, since the input word
matches
the sequencer reference value using the mask value.