Programmer (HHP) User guide

Chapter 8
Using Basic Instructions
8–8
Use an OUT instruction in your ladder program to turn On a bit when rung
conditions are evaluated as true.
An example of a device that turns on or off is an output wired to a pilot light
(addressed as O/4).
OUT instructions are reset when:
You enter or return to the RRUN, RCSN, or RSSN mode or power is
restored.
The OUT is programmed within an inactive or false Master Control Reset
(MCR) zone.
Rung conditions are evaluated as false.
Important: A bit that is set within a subroutine using an OUT instruction
remains set until the subroutine is scanned again.
Entering the Instruction
You enter the instruction from within the program monitor functional area.
0 0 0
B / 0 0
SET and RST are retentive output instructions. SET can only turn on a bit,
while RST can only turn off a bit. These instructions are usually used in
pairs, with both instructions addressing the same bit.
Your program can examine a bit controlled by SET and RST instructions as
often as necessary.
!
ATTENTION: Under fatal error conditions, physical outputs are
turned off. Once the error conditions are cleared, the controller
resumes operation using the data table value of the operand.
( )
Execution Times (µ
sec) when:
True False
4.43 4.43
Ladder representation:
Output
(
O
U
T
)
1
OUT
To access the OUT instruction, press:
False
4.97
(L)
(U)
Execution Times (µ
sec) when:
True
3.16SET
4.97 3.16RST
Ladder representation:
S
e
t
(
SET
)
and
Rese
t
(R
ST
)