User Manual Instruction Manual

Publication 1760-UM002B-EN-P - March 2005
4-44 Wiring with Pico GFX-70
Inputs
The function block inputs >I1 and >I2 can have the following operands:
Constants
Markers MD, MW, MB
Analog inputs IA01 to IA04
IA01: terminal I7
IA02: terminal I8
IA03: terminal I11
IA04: terminal I12
Analog output QA01
Actual value
QV> of another function block
Actual Value QV>
The actual valueQV> can be assigned the following operands:
Markers MD, MW, MB
Analog output QA01
An arithmetic function block is not wired in the circuit diagram.
Parameter display and parameter set for arithmetic function blocks:
Only constants can be modified in the parameter display of a function block.
AR32 ADD +
>I1
>I2
QV>
AR32 Arithmetic function block number 32
ADD Addition mode
+ Appears in the parameter display
>I1 First value
>I2 Second value
QV> Result of the addition