User Manual
Publication 1760-UM003A-EN-P - September 2005
7-60 Pico GFX Control Commands
Set cycle time function block: ST01
(1) Trigger coil. If the coil is triggered (rising edge), the current date, weekday and time of the sending station are
automatically sent to the NET network.
(2) Status 1 if the trigger coil SC01T_ is also 1.
Table 6.187 Telegram Structure
Byte Meaning Value (hex), sent by
Master Slave Master Slave
Attribute ID
Read 92 –
Write B2 –
0 Response:
Read successful – C2
Write successful – C1
Command rejected – C0
0 1 Type 2C 2C
1 2 Instance 01 01
2 3 Index Table 6.188 Table 6.188
3 – 6 4 – 7 Data 1 – 4
Read operation 00 depending on
index,Table 6.189
Write operation depending on
index,Table 6.189
00
Table 6.188 Operand overview
Index
(hex)
Operand read write
00 Bit IO, Table 6.189 x
01 Mode/Parameter – –
02 Cycle time in ms,
value range: 0 – 1000
I1 x
c
(1)
(1) The value can only be written if it is assigned to a constant in the program.