90 DataSite Configuration Settings Utility (DS Settings)
All the states of controller are showed by a 16-bit code. For details, see the
following tables.
If more than one error occurs, an "OR" operation will be performed on the
codes. For example, if both US1 and US2 communication errors occur, the
error code will be 0600. If all errors occur, the code will be 0703.
If more than one initialization state exists, an "OR" operation will be
performed on the codes. For example, a code of 0x0102 means that test
communication and initialization of communication parameters are in
progress.
Clear Error Codes
Follow this step to clear the error codes of the controller.
Click Clear Error
Error codes
Error Code Meaning
0x0001 Hardware register error
0x0002 Data FLASH error
0x0100 HART communication error
0x0200 US1 communication error
0x0400 US2 communication error
Initialization state codes
Initialization State Code Meaning
0x0001 Test communication.
0x0002 Initialize communication parameters.
0x0004 Clear the DataSite Workbench application.
0x0008 Initialize registers.
0x0100 Initialize file system.
0x0200 Initialize DNP3.
DS Workbench Status codes
DS Workbench Status Code Meaning
0001 DataSite Workbench is running.
0000 DataSite Workbench is stopped.