Software User Manual FRN 1.2 Owner manual

Publication 1758-UM002D-EN-P - October 2010
336 Enron Modbus Protocol for the 1758-FLO DataSite Controller
Meter run 5 data variables
Register Data Type Description
3301…3350 Short integer Meter run 5 data variables
Identical structure to meter run 0 data variables.
Offset by a value of 250.
5051…5060 Long integer Meter run 5 data variables
Identical structure to meter run 0 data variables.
Offset by a value of 50.
7501…7600 Float Meter run 5 data variables
Identical structure to meter run 0 data variables.
Offset by a value of 500.
Meter run 6 data variables
Register Data Type Description
3351…3400 Short integer Meter run 6 data variables
Identical structure to meter run 0 data variables.
Offset by a value of 300.
5061…5070 Long integer Meter run 6 data variables
Identical structure to meter run 0 data variables.
Offset by a value of 60.
7601…7700 Float Meter run 6 data variables
Identical structure to meter run 0 data variables.
Offset by a value of 600.