296 Extension Modbus Protocol for DataSite Controllers (1758-FLO)
There is no event code for command number 15.
49036 float W Upper alarm limit of differential
pressure or pulse
49038 float W Lower alarm limit of differential
pressure or pulse
49040 float W Alarm dead-band of differential
pressure or pulse
49042 u_short W Enable or disable static pressure
alarm
0: Disable
1: Enable
49043 float W Upper alarm limit of static
pressure
49045 float W Lower alarm limit of static
pressure
49047 float W Alarm dead-band of static
pressure
49049 u_short W Enable or disable temperature
alarm
0: Disable
1: Enable
49050 float W Upper alarm limit of temperature
49052 float W Lower alarm limit of temperature
49054 float W Alarm dead-band of temperature
Return codes for command number 15
Return Code Description
00 OK
01 Meter run is invalid
02 The input value for differential pressure or pulse alarm setting is
invalid
03 The input value for static pressure alarmsetting is invalid
04 The input value for disable temperature alarmsetting is invalid
100 Pass code is incorrect
Other Invalid
Parameters for command number 15 (Continued)
Address Data Type Attribute Description