Software User Manual FRN 1.2 Owner manual

Publication 1758-UM002D-EN-P - October 2010
Extension Modbus Protocol for DataSite Controllers (1758-FLO) 289
There is no event code for command number 8.
Command Number 9: Set Up the Input Signal Test
Use command number 9 to set up the input signal test for one meter run.
49035 u_short R Contract hour (0…23)
49036 u_short R Contract minute (0…59)
49037 u_short Reserved
Return codes for command number 8
Return Code Description
00 OK
100 Pass code is wrong
Other Invalid
Parameters for command number 9
Address Data Type Attribute Description
49025 u_short RW 9
49026 u_short R Return code
49027 u_short W Meter run (0…7)
49028 u_int W Pass code for user
49030…49034 Reserved
49035 u_short W Whether differential pressure or
pulse tested.
0: No test
1: Test
49036 u_short W Whether static pressure tested.
0: No test
1: Test
49037 u_short W Whether temperature tested.
0: No test
1: Test
49038 float W Differential pressure or pulse test
value
49040 float W Static pressure test value
49042 float W Temperature test value
Parameters for command number 8 (Continued)
Address Data Type Attribute Description